Cable Voltage Drop

Voltage drop along a low-voltage cable run and the smallest section that keeps it within the limit, using the resistive method common in installation practice.

ElectricalCable sizingInstallation
↑ ↓ steps the value
Voltage drop1.67 %
Voltage drop ΔU
6.7 V
Line current I
25.5 A
Power loss in cable
348 W
Section needed for the limit
3.35 mm²
Suggested standard section
4 mm²
  • Drop 1.67 % — limit 3.0 %
  • Check current-carrying capacity for the installation method separately (manufacturer tables)
METHOD

How it is calculated

Single-phase: ΔU = 2 · L · I · cos φ / (κ · S)
Three-phase:  ΔU = √3 · L · I · cos φ / (κ · S)
I = P / (U · cos φ)   ·   I = P / (√3 · U · cos φ)
ASSUMPTIONS & NOTES
  • κ: copper 56, aluminium 35 m/(Ω·mm²) at 20 °C. Resistance rises ≈ 20 % at operating temperature.
  • Line reactance is ignored; include it for sections above 50 mm² and long runs.
  • Common limits: lighting 1.5 %, power 3 %; current-carrying capacity must also be checked.

Results are for preliminary design and checking; base the final design on the governing standard and safety factors.