Motor Current

Supply current and starting currents of a three- or single-phase induction motor from its nameplate data — the first step in sizing breakers, fuses and cables.

ElectricalMotorStarting
↑ ↓ steps the value
Rated current I_N14.5A
Active power drawn
8.43 kW
Apparent power S
10.03 kVA
Reactive power Q
5.44 kVAr
Direct-on-line starting current
101 A
Star-delta starting current (≈ 1/3)
34 A
Rated torque T_N
49.1 N·m
METHOD

How it is calculated

I_N = P / (√3 · U · cos φ · η)      (three-phase)
S = P / (η · cos φ)      Q = S · sin φ
I_start ≈ (5…8) · I_N   ·   star-delta ≈ 1/3
ASSUMPTIONS & NOTES
  • P is the nameplate shaft power.
  • Soft starters and drives can limit starting current to about 2–4·I_N.

Results are for preliminary design and checking; base the final design on the governing standard and safety factors.