Heating – Cooling Load

Heat needed to warm or cool a fluid without phase change — the starting point for sizing heat exchangers, boilers, chillers and process heaters.

HeatHVACProcess
↑ ↓ steps the value
Heat load Q̇46.37kW
Heat load
39,874 kcal/h
Heat load
158,234 BTU/h
Mass flow ṁ
0.5544 kg/s
Volume flow
33.33 L/min
Temperature difference ΔT
20 K
METHOD

How it is calculated

Q̇ = ṁ · c_p · ΔT
ṁ = ρ · V̇
Water rule of thumb: Q̇[kW] ≈ 1.163 · V̇[m³/h] · ΔT
ASSUMPTIONS & NOTES
  • Latent heat (evaporation or condensation) is not included.
  • 1 kW = 859.8 kcal/h = 3412 BTU/h.

Results are for preliminary design and checking; base the final design on the governing standard and safety factors.